7 Application Instructions API 50-99 Output: Y0 or Y2 Pulse speed (Hz) Time interval among pulse outputs = x 1/10 S 3 Targeted speed: 10 ~ 200,000Hz 16-bit command:110~32,767PLS 32-bit command:110~2,147,483,647PLS 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9 1010 Every speed variation = x 1/10 S 1 S 2 10-step variations 10-step variations Time(Sec) Decel time below 5,000ms Accel time below 5,000ms ( ) S 3 ( ) S 3 Remarks: 1. The outputs cannot be the same as those of API 57 PLSY and API 58 PWM. 2.

When there are many high speed pulse output instructions (PLSY, PWM, PLSR) in a program for Y0 output, and provided these instructions are being executed in the same scan period, PLC will set up and output the instructions with the fewest steps. 3. With M1133 ~ M1135 and D1133, Y0 of SA/SX/SC series MPU can output pulses at up to 50kHz. (SX V3.0 and above do not support this function. Users can directly use PLSY to output pulses at 50kHz.) See 2.11 for more details of special D and special M. Range of output frequecies for all series: 4. Flags and special registers for SA/SC series MPU: DVP-PLC APPLICATION MANUAL 7-40 M PU ES/EX/SS SA/SX/SC EH EH2/SV/EH3/SV2 Range Y0: 10 ~ 10,000Hz Y1:

10 ~ 10,000Hz Y0: 10 ~ 30,000Hz Y1: 10 ~ 30,000Hz Y0: 10 ~ 200,000Hz Y2: 10 ~ 200,000Hz Y0: 10 ~ 200,000Hz Y2: 10 ~ 200,000Hz Y4: 10 ~ 200,000Hz Y6: 10 ~ 200,000Hz M1347 For SA/SC. Reset flag for Y0 pulse output (Available in SA V1.8 and later version, SC V1.6 and later versions) M1348 For SA/SC. Reset flag for Y1 pulse output (Availabe in SA V1.8 and later versions, SC V1.6 and later versions) M1524 For SC (V1.6 and later versions). Reset flag for Y10 pulse output M1525 For SC (V1.6 and later versions). Reset flag for Y11 pulse output