9 Application Instructions API 150-199 D1349: High word of the current number of Y10 output pulses. D1350: Low word of the current number of Y11 output pulses. D1351: High word of the current number of Y11 output pulses.. D1340: Settings of the first start frequency and the last end frequency of Y10 output pulses. D1352: Settings of the first start frequency and the last end frequency of Y11 output pulses. D1343: Settings of the acceleration/deceleration time of Y10 output pulses. D1353: Settings of the acceleration/deceleration time of Y11 output pulses. 5. Flags for EH/EH2/SV/EH3/SV2 series MPU: M1010:
For EH/EH2/SV/EH3/SV2, when M1010 = On, CH0, CH1, CH2 and CH3 will output pulses when END instruction is being executed. M1010 will be Off automatically when the output starts. M1029: For EH/EH2/SV/EH3/SV2, M1029 = On after CH0 pulse output is completed. M1030: For EH/EH2/SV/EH3/SV2, M1030 = On after CH1 pulse output is completed. M1036: For EH2/SV/EH3/SV2, M1036 = On after CH2 pulse output is completed. M1037: For EH2/SV/EH3/SV2, M1037 = On after CH3 pulse output is completed. M1119 For EH2/SV/EH3/SV2, the instruction DDRVI/DDRVA is enabled when M1119 is On. M1257 For EH2/SV/EH3/SV2, the acceleration/deceleration slope of the high-speed pulse output is an S curve. M1305:
For EH/EH2/SV/EH3/SV2, direction signal of CH0. M1306: For EH/EH2/SV/EH3/SV2, direction signal of CH1. M1334: For EH, CH0 pulse output pauses. For EH2/SV/EH3/SV2, CH0 pulse output stops. M1308 For EH/EH2/SV/EH3/SV2, Off->On: The first high-speed pulse output CH0 (Y0, Y1) pauses immediately. On->Off: Continuing to output the pulses which have not been output M1309 For EH/EH2/SV/EH3/SV2, Off->On: The first high-speed pulse output CH1 (Y2, Y3) pauses immediately. On->Off: Continuing to output the pulses which have not been output M1310 For EH/EH2/SV/EH3/SV2, On->Off: Continuing to output the pulses which have not been output Off->On:
The first high-speed pulse output CH2 (Y4, Y5) pauses immediately. M1311 For EH/EH2/SV/EH3/SV2, Off->On: The first high-speed pulse output CH3 (Y6, Y7) pauses immediately. On->Off: Continuing to output the pulses which have not been output M1335: For EH, CH1 pulse output pauses. For EH2/SV/EH3/SV2, CH1 pulse output stops. M1336: For EH/EH2/SV/EH3/SV2, “CH0 sends out pulses” indication. M1337: For EH/EH2/SV/EH3/SV2, “CH1 sends out pulses” indication. M1347: For EH2/SV/EH3/SV2 (V1.4 and later versions). Reset flag for CH0 pulse output. DVP-PLC Application Manual 9-54