User Manual EM303B General Purpose Inverter Command code 0x08: Circuit Diagnosis and Setting Remarks: Command code 0x08 is only for circuit check. 13.5 Description of Protocol Format 13.5.1 Address Code Address of slave inverter. The setting range: 1~247, 0 is broadcast address. 13.5.2 Command Code 13.5.3 Allocation of Register Addresses 179 ADU Item Byte No. Range Master requests: Address of slave 1 0~127 Command code 1 0x08 Sub-function code 2 0x0000~0xFFFF Register data 2 CRC parity 2 Slave responds:

Address of slave 1 Inverter address Command code 1 0x08 Sub-function code 2 0x0000~0xFFFF Register data 2 CRC parity 2 Command Code Function 03H Read parameters and status byte of inverter 06H Write single function code or control parameter of inverter 10H Write several function codes or control parameters of inverter 08H Circuit diagnosis and setting Name Address Description 0000H~1F1FH (Saving Address) High byte is the function code group number. F0~FF, C0, and E0 are corresponding to high bytes: 00H~0FH, 10H, and 11H respectively. Low byte is serial number of function code group. 0~31 corresponding to low bytes 00H~1FH. For example: the corresponding saving address of F0-06 is 0006H.

The saving address is prohibited for the function codes which are modified frequently. Otherwise, the EEPROM of inverter may be damaged, and inverter will trip fault EEd. Function Code 2000H~3F1FH (Temporary Saving Address) For frequent modified function codes, the function code address +2000H is to prevent EEPROM of inverter from being damaged. Due to frequent modification, the value of this function code will not be saved at power failure. For example, the temporary saving address of F0-06 is