User Manual EM303B General Purpose Inverter 13.7 Example Read primary numeric frequency setting (F0-07) of Inverter No.01, return 50Hz. Write F0-07=30.00Hz, the setting value of primary numeric frequency of Inverter No.01. (Recommended to Apply ) Write F0-09 =5.00 seconds, the acceleration time 1 of Inverter No.01. Remarks: For frequent modified function codes, the function code address +2000H is to prevent the EEPROM of inverter from being damaged.
Inverter Starts Inverter Stops 183 Transmitting 0 1 2 3 4 5 6 7 8 9 Sequence Data 01H 03H 20H 07H 00H 01H 3EH 0BH Receiving 0 1 2 3 4 5 6 7 8 Sequence Data 01H 03H 02H 13H 88H B5H 12H Transmitting 0 1 2 3 4 5 6 7 8 9 Sequence Data 01H 06H 70H 01H 0BH B8H C5H 88H Receiving 0 1 2 3 4 5 6 7 8 9 Sequence Data 01H 06H 70H 01H 0BH B8H C5H 88H Transmitting 0 1 2 3 4 5 6 7 8 9 Sequence Data 01H 06H 00H 09H 01H F4H 59H DFH Receiving 0 1 2 3 4 5 6 7 8 9 Sequence Data 01H 06H 00H 09H 01H F4H 59H DFH Transmitting 0 1 2 3 4 5 6 7 8 9 Sequence Data 01H 06H 40H 00H 00H 01H 5DH CAH Receiving 0 1 2 3 4 5 6 7 8 9 Sequence Data 01H 06H 40H 00H 00H 01H 5DH CAH Transmitting 0 1 2 3 4 5 6 7 8 9 Sequence