User Manual EM303B General Purpose Inverter F0-06 Forselecting the source of regular speed setting signal. F0-06=0 Primary numeric frequency setting mode is defined by the value of F0-07. F0-06=1 Setting frequency is set by VP keypad potentiometer. F0-06=2 Setting frequency is set by the voltage of analog terminal VS. F0-06=3 Setting frequency is set by the current of analog terminal IS.

F0-06=4 Not used F0-06=5 Setting frequency is set by K3*VS+K4*IS (Input VS and IS signals) F0-06=6 Setting frequency is set by K3*VS+K5*VF (Input VS and VF voltage signals) F0-06=7 Setting frequency is set by K4*IS+K6*IF (Input IS and IF current signals) F0-06=8 Setting frequency is set by the greater value between K3*VS and K5*VF (Inputs of terminals VS and VF) F0-06=9 Setting frequency is set by the greater value between K4*IS and K6*IF (Inputs of terminals IS and IF) F0-06=10 Setting frequency is set by all input signals:

K1*VP+K2*(K3*VS+K4*IS+K5*VF+K6*IF-K8*5V) ★ The combination of analog voltage signal and analog current signal can be considered as that the current signal linearly switched to voltage signal of 0-10V first, and then calculate. 1. The default of analog voltage inputs VS and VF:0 ~ 10V. 2. The default of analog current input: 4 ~ 20mA. 3. K1 ~ K8 are analog signal gains which can be set by F1-22 ~ F1-29. F0-07 Thesetting value of primary numeric frequency, and the range: 0.00 ~ Fmax. ★ Press or to edit the value of F0-07 in running preparation and running status. Acceleration time is the time taken for the output frequency to rise from 0Hz up to maximum frequency Fmax set by F0-16.

Deceleration time is the time taken for the output frequency to drop from Fmax down to 0Hz, which are not relevant to forward and reverse. As shown in Figure 7-4. 86 No. Function Range Unit Default Type F0-07 Primary Numeric Frequency Setting 0.00~Fmax Hz 0.00 ● No. Function Range Unit Default Type F0-09 Acceleration Time 1 0.00~600.00 S/min 15.00 ● F0-10 Deceleration Time 1 0.00~600.00 S/min 15.00 ●