EM500 Open-Loop Vector Control Inverter User Manual 108 change the time set in F09.21has arrived 2: Start calculating integral item when the error is less than F09.38 F09.38 PID Integral Action Given Change Ttime Input Deviation 0.00-100.00 % 30.00 ● F10 Communication Function Group F10.00 Inverter Address 1 - 247, 0 as broadcasting address 1 〇 F10.01 Modbus Communication Bit Rate 0: 4800 1: 9600 2: 19200 3: 38400 4: 57600 5: 115200 1 〇 F10.02 Modbus Data Format 0: 1-8-N-1 (1 start bit + 8 data bits +1 stop bit) 1: 1-8-E-1 (1 start bit + 8 data bits + 1 even parity + 1 stop bit) 2: 1-8-O-1 (1 start bit + 8 data bits + 1 odd parity + 1 stop bit) 3:
1-8-N-2 (1 start bit + 8 data bits +2 stop bits) 4: 1-8-E-2 (1 start bit + 8 data bits + 1 even parity +2 stop bits) 5: 1-8-O-2 (1 start bit + 8 data bits + 1 odd parity +2 stop bits) 0 〇 F10.03 Modbus Overtime 0.0 - 60.0, 0.0: Disabled (also works for master - slave system) s 0.0 ● F10.04 Modbus Response Delay 1 - 20 ms 2 ● F10.05 Master-Slave Communication Function 0: Disabled 1: Enabled 0 〇 F10.06 Master-Slave Options 0: Slave 1: Master (Modbus protocol) 2: Master (CANSinee protocol) 0 〇 F10.07 Data Sent by Master 0: Output Frequency 1: Set Frequency 2: Output Torque 3: Set Torque 1 〇