sinee — 6.2 Function Parameter Table

EM500 Open-Loop Vector Control Inverter User Manual 107 Variation Time F09.22 PID Feedback Filter Time 0.000 - 30.000 s 0.000 ● F09.23 PID Output Filter Time 0.000 - 30.000 s 0.000 ● F09.24 Upper Limit Detection Value of PID Feedback Disconnection 0.00 - 100.00 100.00=Feedback Disconnection Disabled % 100.00 ● F09.25 Lower Limit Detection Value of PID Feedback Disconnection 0.00 - 100.00 0.00=Feedback Disconnection Disabled % 0.00 ● F09.26 PID Feedback Disconnection Detection Time 0.000 - 30.000 s 0.000 ● F09.27 PID Sleep Control 0: Disable 1: Enable 2: Lower Limit Frequency Enable 3:

No Output Enable 0 ● F09.28 Sleep Action Point 0.00 - 100.00 (100.00 corresponds to PID Setting Feedback Range) % 100.00 ● F09.29 Sleep Delay Time 0.0 - 6500.0 s 0.0 ● F09.30 Awakening Action Point 0.00 - 100.00 (100.00 corresponds to PID Setting Feedback Range) % 0.00 ● F09.31 Awakening Delay Time 0.0 - 6500.0 s 0.0 ● F09.32 Preset PID Setting 1 0.0 – PID Setting Feedback Range F09.03 0.0 ● F09.33 Preset PID Setting 2 0.0 – PID Setting Feedback Range F09.03 0.0 ● F09.34 Preset PID Setting 3 0.0 – PID Setting Feedback Range F09.03 0.0 ● F09.35 The Feedback Voltage Upper Limit The feedback voltage lower limit~10.00 V 10.00 ● F09.36 The Feedback Voltage Lower Limit 0.00~ The Feedback Voltage Upper Limit V 0.00 ● F09.37 PID Integral Action Choice in time of 0:

Always calculate integral item 1: Start calculating Integral item When 0 ●