EM500 Open-Loop Vector Control Inverter User Manual Final setting frequency is determined through main and auxiliary arithmetic results (refer to F00.08). Frequency Source B F00.06=3: Switching between Main Frequency Source A and Auxiliary Final setting frequency is determined through input function “26: Frequency Source Switching”. If the input function is disabled, final setting frequency is determined by main frequency source A; if the input function is enabled, final setting frequency is determined by auxiliary frequency source B. F00.06=4: Switching between Main Frequency Source A and Main & Auxiliary Arithmetic Results Final setting frequency is determined through input function “26:
Frequency Source Switching”. If the input function is disabled, final setting frequency is determined by main frequency source A; if the input function is enabled, final setting frequency is determined by main and auxiliary arithmetic results. See F00.08 for details. F00.06=5: Switching between Auxiliary Frequency Source B and Main & Auxiliary Arithmetic Results Final setting frequency is determined through input function “26: Frequency Source Switching”. If the input function is disabled, final setting frequency is determined by auxiliary frequency source B; if the input function is enabled, final setting frequency is determined by main and auxiliary arithmetic results.
See F00.08 for details F00.07 is used to set the numeric frequency, with its maximum value limited by the maximum frequency (F00.16) 161 No. Function Range Unit Default Type F00.07 Numeric Frequency Setting 0.00 Hz - Maximum Frequency Hz 50.00 ● No. Function Range Unit Default Type F00.08 Main and Auxiliary Arithmetic 0: Main Frequency Source A + Auxiliary Frequency Source B 0 〇