sinee — 7.1 F00 Group: General Parameter

EM500 Open-Loop Vector Control Inverter User Manual Generally, it is used for on-site closed loop control mode, for example closed loop control under constant pressure and closed loop control under constant tensile force. F00.05=11: Simple PLC Auxiliary frequency B is determined by the output of Simple PID (refer to 7.9). 1. User can not select the same terminal (AI1-4/X7) for main frequency source A and auxiliary frequency source B; 2. Process PID or simple PLC will be enabled only after being selected. Select final frequency setting channel and arithmetic mode. F00.06=0: Main Frequency Source A Final setting frequency is only determined through main frequency source A. F00.06=1:

Auxiliary Frequency Source B Final setting frequency is only determined through auxiliary frequency source B. F00.06=2: Main and Auxiliary Arithmetic Results 160 No. Function Range Unit Default Type F00.06 Frequency Source Options 0: Main Frequency Source A 1: Auxiliary Frequency Source B 2: Main and Auxiliary Arithmetic Results 3: Switching between Main Frequency Source A and Auxiliary Frequency Source B 4: Switching between Main Frequency Source A and Main & Auxiliary Arithmetic Results 5: Switching between Auxiliary Frequency Source B and Main & Auxiliary Arithmetic Results 6:Auxiliary Frequency Source B+ Feedforward arithmetic(Winding application) 0 〇