EM500 Open-Loop Vector Control Inverter User Manual password protection function is disabled. After setting the user password (none 0), in addition to the function code, all the parameters can only be viewed, cannot be modified. F00.30=0 Set inverter as Type G, which applies to mechanical and constant torque load; F00.30=1 Set inverter as Type P, which applies to fan, water pump and other square or cubic load. ★ When inverter is set as Type P, please refer to motor nameplate for applicable motor power. Make sure that it cannot be applied to constant torque load at this type. 7.2 F01 Group: Motor 1 Parameter EM500 supports the induction motor and the synchronous motor.
Please set this parameter according to actual applications. 171 No. Function Range Unit Default Type F00.30 Inverter Type 0: G 1: P 0 〇 No. Function Range Unit Default Type F01.00 Motor Type 0: Common Induction Motor 1: Inverter Induction Motor 2: Permanent Magnet Synchronous Motor 0 〇 No.
Function Range Unit Default Type F01.01 Motor Rated Power 0.10 - 650.00 kW Up To Specific Model 〇 F01.02 Motor Rated Voltage 50 - 2000 V Up To Specific Model 〇 F01.03 Motor Rated Current 0.01 - 600.00 (Motor Rated Power ≤ 75kW) 0.1 - 6000.0 (Motor Rated Power >75kW) A Up To Specific Model 〇 F01.04 Motor Rated Frequency 0.01 - 600.00 Hz Up To Specific Model 〇 F01.05 Motor Rated Speed 1 - 60000 rpm Up To Specific 〇