EM500 Open-Loop Vector Control Inverter User Manual Function codes mentioned above are nameplate parameters of induction motor. For the first time when inverter is wired to motor, please set the parameters above as per motor nameplate before inverter running, regardless of the control mode, VF control mode or vector control mode. When motor rated power (F01.01) is set, inverter will modify the values of the parameters of F01.03 - F01.08 automatically. Please pay attention while using inverter. F01.09 - F01.13 are parameters of induction motor. However, user can not get these parameters generally. Please autotune motor parameters by using F01.34.
After motor parameters of F01.01 - F01.08 are modified, inverter will modify the 172 Model F01.06 Motor Winding Connection 0: Y 1: Δ Up To Specific Model 〇 F01.07 Motor Rated Power Factor 0.600 - 1.000 Up To Specific Model 〇 F01.08 Motor Efficiency 30.0 - 100.0 % Up To Specific Model 〇 No.
Function Range Unit Default Type F01.09 Stator Resistor of Induction Motor 1 - 60000 (Motor Rated Power ≤ 75kW) 0.1 -6000.0 (Motor Rated Power >75kW) mΩ Up To Specific Model 〇 F01.10 Stator Resistor of Induction Motor 1 - 60000 (Motor Rated Power ≤ 75kW) 0.1 - 6000.0 (Motor Rated Power >75kW) mΩ Up To Specific Model 〇 F01.11 Leakage Inductance of Induction Motor 0.01 - 600.00 (Motor Rated Power ≤ 75kW) 0.001 - 60.000 (Motor Rated Power >75kW) mH Up To Specific Model 〇 F01.12 Mutual Inductance of Induction Motor 0.1 - 6000.0 (Motor Rated Power ≤ 75kW) 0.01 - 600.00 (Motor Rated Power >75kW) mH Up To Specific Model 〇 F01.13 Idling Excitation Current of Induction Motor 0.01 - 600.00 (Motor Rated Power ≤ 75kW) 0.1 - 6000.0 (Motor Rated Power >75kW) A Up To Specific Model 〇