sinee — 7.3 F02 Group: Input Terminal Parameter

EM500 Open-Loop Vector Control Inverter User Manual When input pulse frequency changes fast or the system does not need to make a quick response to the input pulse, user may properly increase the filter time to stabilize the system. Analog input terminals AI1 - AI4 of EM500 inverter can be used as numeric terminals. User only needs to set them as 1. If terminal AI2 is used as a numeric terminal, i.e., F02.31=xx1x, its analog input and numeric logic are switched as follows:  When the terminal input voltage ;  When the terminal input voltage >3V, the corresponding logic status is enable ;  When the terminal input voltage falls between 1V and 3V, corresponding logic remains.

Logic TT 1 0 0 V 1V 3V Voltage TT Figure 7-11 Analog Input Terminal Voltage and Present Logic Status Relationship 189 No. Function Range Unit Default Type F02.31 Analog Input Function Ones Place: AI1 0: Analog Input 1: Numeric Input (0 for less than 1V, 1 for over 3V, contrary to the last time for 1V-3V) Tens Place: AI2 0: Analog Input 1: Numeric Input (the same as above) Hundreds Place: AI3 0: Analog Input 1: Numeric Input (the same as above) Thousands Place: AI4 (expansion card) 0: Analog Input 1: Numeric Input (the same as above) 0000D 〇