EM500 Open-Loop Vector Control Inverter User Manual ★ If the function code is set as 0.000s, the delay is disabled accordingly. EM500 inverter supports high-speed pulse input (HDI) function, and terminal X7 is shared. F02.26 - F02.30 are used to set the pulse filter time and corresponding offset curve. As indicated in Figure 7-10, the system realizes the line offset through the setting of the two points (F02.26, F02.27) and (F02.28, F02.29) according to the input pulse frequency size, and the input outside the frequency range will be cut off.
Offset Output 100.0% F02.29 1 1 ( , ) X Y 100.00 0 F02.26 F02.28 Pulse Frequency/kHz 脉冲频率/ kHz F02.27 0 0 ( , ) X Y -100.0% Figure 7-10 High-Speed Pulse Input Offset Curve 188 No. Function Range Unit Default Type F02.26 Minimum Input Pulse Frequency 0.00 - Maximum Input Pulse Frequency F02.28 kHz 0.00 ● F02.27 Setting Corresponding to Minimum Input –100.0 - +100.0 % 0.0 ● F02.28 Maximum Input Pulse Frequency 0.01 - 100.00 kHz 50.00 ● F02.29 Setting Corresponding to Maximum Input –100.0 - +100.0 % 100.0 ● F02.30 Pulse Input Filter Time 0.00 - 10.00 s 0.10 ●