sinee — 7.3 F02 Group: Input Terminal Parameter

EM500 Open-Loop Vector Control Inverter User Manual mode, when inverter is reading terminal status, the multi-function input terminal signal have to be processed by digital filtering in order to avoid interference. ★ This code does not need to be adjusted on general conditions. When an adjustment is required, please note the relations between filter times and lasting time when terminal is on. It is to avoid that inverter is easy to be interfered with due to insufficient filter times, or slow response or command loss due to too many filter times.

XiTT Xi Input TTTT Delay Effective Delay Ineffective Delay Figure 7-9 Terminal Delay Sampling The terminal will delay to response according to the function code setting when the function terminal status changes. At present, terminals X1 - X4 support this function. Specific actions: this function will be active after the function terminal changes from disabled status to enabled status and the effective delay time is reached; this function terminal becomes inactive after the function terminal changes from enabled status to disabled status and the ineffective delay time is reached. 187 No.

Function Range Unit Default Type F02.18 X1 Effective Delay Time 0.000 - 30.000 s 0.000 ● F02.19 X1 Ineffective Delay Time 0.000 - 30.000 s 0.000 ● F02.20 X2 Effective Delay Time 0.000 - 30.000 s 0.000 ● F02.21 X2 Ineffective Delay Time 0.000 - 30.000 s 0.000 ● F02.22 X3 Effective Delay Time 0.000 - 30.000 s 0.000 ● F02.23 X3 Ineffective Delay Time 0.000 - 30.000 s 0.000 ● F02.24 X4 Effective Delay Time 0.000 - 30.000 s 0.000 ● F02.25 X4 Ineffective Delay Time 0.000 - 30.000 s 0.000 ●