EM500 Open-Loop Vector Control Inverter User Manual 1: enabled when the multi-function input terminal is off, disabled when the multi-function input terminal is on 1 while setting them. Take F02.15 as example (see the table below): Such function codes are under the bit operation. Set corresponding position as 0 or Table 7-5 Function Code of Bit Operation have any meaning. The 7 th bit will not be used. This bit can not be set and the displayed value does not For example: set X1 to negative logic by setting its corresponding bit 0 as 1, i.e., F02.15=xxx xxxx1. corresponding bit of X6 as 1, i.e., 02.15=xx1 xxxx1.
Set X1 and X6 to negative logic by setting corresponding bit 0 of X1 and ★ This function is used for matching with the logic of other peripherals Sampling clock 1m Xi input s Note: Assuming that the anti-shake Anti-Interference The interference is less than the anti- The interference is greater than the anti-shake filter times is the default value 2 Note: Assuming that anti-shake filter times is the default value 2 shake filter times filter times Figure 7-8 Terminal Filter Sampling Because multi-function input terminals adopt level triggered mode or pulse triggered 186 Item * X7 X6 X5 X4 X3 X2 X1 Bit 7 6 5 4 3 2 1 0 Value * 0/1 0/1 0/1 0/1 0/1 0/1 0/1 No.
Function Range Unit Default Type F02.17 Filter Times of Numeric Input Terminal 0-100, 0 for No Filter, n for sampling once every n ms 2 〇