sinee — 7.4 F03 Group: Output Terminal Function Parameter

EM500 Open-Loop Vector Control Inverter User Manual Table 7–6 Numeric Multi-Function Output Terminals 193 Value Function Description 0 No Output Set “0: No Function” for an unused or fault terminal to prevent false output. 1 Inverter Running (RUN) When inverter is in slave running, slave stop, JOG running or JOG stop status, present output is active; in other status, present output is inactive.

2 Frequency Reach Range (FAR) When inverter is in running status and the absolute value of “output frequency – the set frequency” ≤ frequency reach detection width (F15.20), present output is active; when inverter is not in running status or the absolute value of “output frequency – the set frequency” > frequency reach range (F15.20), present output is inactive. See the function code F15.20 for details.

3 Output Frequency Detection Range FDT1 When inverter is in running status, and the absolute value of output frequency > output frequency detection range FDT1 (F15.21), then present output is active; when inverter is not in running status, or the absolute value of output frequency ≤ output frequency detection range FDT1 (F15.21) - hysteresis FDT1 (F15.22), present output is inactive; for other status, present output status remains unchanged.

See the Function Codes F15.21 and F15.22 for details 4 Output Frequency Detection Range FDT2 When inverter is in running status, and the absolute value of output frequency > output frequency detection range FDT1 (F15.23), then present output is active; when inverter is not in running status, or the absolute value of output frequency ≤ output frequency detection range FDT2 (F15.23) - hysteresis FDT1 (F15.24), present output is inactive; for other status, present output status remains unchanged. See the function codes F15.23 and F15.24 for details.

5 Reverse Running (REV) When the running direction and acceleration/deceleration status of inverter are reverse acceleration, reverse deceleration or reverse constant speed, present output is active. 6 JOG Running When inverter is in JOG running or JOG stop status, present output is active. In other status, present output is inactive