sinee — 7.4 F03 Group: Output Terminal Function Parameter

EM500 Open-Loop Vector Control Inverter User Manual 194 7 Inverter Fault When inverter is in fault status, present output is active; in other status, present output is inactive. 8 Inverter Ready When inverter is ready for running after it is powered on and finishes initialization without any abnormality, present output is active. 9 Upper Limit Frequency Reach When inverter is in JOG or slave running status, output frequency (F18.00) ≥ the upper limit frequency (F00.17||F00.18) and the set frequency (F18.01) ≥ the upper limit frequency (F00.17||F00.18), present output is active. Otherwise, present output is inactive.

10 Lower Limit Frequency Reach When inverter is in JOG or slave running status, output frequency (F18.00) ≤ the lower limit frequency (F00.19) and the set frequency (F18.01) ≤ the lower limit frequency (F00.19), present output is active. Otherwise, present output is inactive. 11 Current Limit Reach When output current (F18.06) ≥ current limit level (F07.12), present output is active. When output current (F18.06) ≤ current limit level (F07.12) -5.0%, present output is inactive. When the voltage is the intermediate value, present output status remains the same.

12 Overvoltage Stall Voltage Reach When output voltage (F18.07) ≥ Overvoltage stall control voltage (F07.07), present output is active. When output voltage (F18.07) ≤ Overvoltage stall control voltage (F07.07) -10V, present output is inactive. When the voltage is the intermediate value, present output status remains the same.

13 Simple PLC Cycle Finished When the simple PLC running mode is “stop after single running” (F18.15=0), inverter stops after single running, and present output is active; when the simple PLC running mode is “stop after limited times of running” (F18.15=1), inverter stops after running as per F08.16, present output is active; otherwise (run again, simple PLC status reset, etc.), present output is inactive. 14 Set Count Value Reach When input pulse count value (F18.34) ≥ set count value (F16.03), present output is active, otherwise the output is inactive. See the function codes F16.03 - F16.04 for details. 15 Designated Count When input pulse count value (F18.34) ≥designated count