sinee — 7.4 F03 Group: Output Terminal Function Parameter

EM500 Open-Loop Vector Control Inverter User Manual 195 Value Reach value (F16.04), present output is active, otherwise the output is inactive. See the function codes F16.03 - F16.04 for details. 16 Length Reach When the input pulse conversion value (F18.34) ≥ the set count value (F16.01), present output is active, otherwise the output is inactive. See the function codes F16.01 - F16.02 for details. 17 Motor Overload Pre-alarming When present motor current ≥ motor pre-alarming factor (F07.02), present output is active. Otherwise, the output is inactive.

18 Inverter Overheating Pre-Alarming When inverter temperature >= overheat spot -25℃, the pre-alarming output is active, otherwise the pre-alarming output is inactive. 19 PID Feedback Upper Limit Reach If PID feedback (F18.17) ≥ the upper limit of PID output (F09.16) when inverter is running, present output is active. Otherwise, present output is inactive. 20 PID Feedback Lower Limit Reach If PID feedback (F18.17) ≤ the lower limit of PID output (F09.17) when inverter is running, present output is active. Otherwise, present output is inactive.

21 Analog Input Level Detection ADT1 If the selected analog input channel ≥ the analog input level detection (F15.26/28), corresponding output is active; if the selected analog input channel ≤ the analog input level detection (F15.26/28) – the hysteresis (F15.27/29), present output is inactive; When inverter is in other status except the two above, present output status remains the same. See F15.25 - F15.29 for details. 22 Analog Input Level Detection ADT2 23 Not Used 24 Undervoltage Status When DC bus voltage (F18.08) ≤ undervoltage stall control voltage (F07.08), present output is active.

When DC bus voltage (F18.08) ≥ Judgment Voltage at Power Failure Ending (F07.09), and maintenance time ≥ judgment delay time at power failure ending (F07.10), present output is inactive. 25 Motor Overload Pre-alarming When present motor temperature (F18.38) ≥ motor overheating pre-alarming threshold (F07.05), present output is active. Otherwise, the output is inactive. See F07.03 - F07.05 for details.