sinee — 7.7 F06 Group: Vector Control Parameter

EM500 Open-Loop Vector Control Inverter User Manual F06.09=5: the torque limit is set by communication If it’s master-slave communication (F10.05=1) and the inverter is slave (F10.06=0), the torque limit is “700FH (communication setting) * 250.0% * F10.08 (proportional coefficient”. The range of 700FH is 0.00% to 100.00%. Details are shown on table 12-2. (communication setting) * F06.10/ F06.11”. The range of 7019H is 0.00% to 250.0%. If it’s general communication (F10.05=0) the torque limit is “7019H Details are shown on table 12-2. 1. This code indicates the ratio between the output torque at the torque limit and inverter rated output torque. 2.

User can set the upper limit of the torque as per actual demands to protect motor or meet the operating mode requirements 3. The electric mode and the brake mode shall be set separately. Current loop PID regulator parameter can directly affect system performance and stability. On general conditions, user does not have to change the default value. The simple servo function is effective to synchronous motor control, gain adjustment can increase system rigidity. 220 No. Function Range Unit Default Type F06.12 Excitation Current Proportional Gain ACR-P1 0.00 - 100.00 0.50 ● F06.13 Excitation Current Integral Time Constant ACR-T1 0.00 - 600.00 0.00:

No Integral ms 10.00 ● F06.14 Torque Current Proportional Gain ACR-P2 0.00 - 100.00 0.50 ● F06.15 Torque Current Integral Time Constant ACR-T2 0.00 - 600.00 0.00: No Integral ms 10.00 ● No. Function Range Unit Default Type F06.16 Position Loop Gain 0.000 - 40.000 1.000 ●