sinee — 7.7 F06 Group: Vector Control Parameter

EM500 Open-Loop Vector Control Inverter User Manual Motor speed goes down as load increases. To ensure that rotor speed gets close to synchronous rotation speed under motor rated load and slip compensation can be enabled. If motor speed goes below the target value, increase the value set through F06.08. When inverter is in SVC control mode, this parameter is used to adjust the speed stability accuracy of motor: if the accuracy is relatively lower, increase the value set by the parameter and vice versa. This function code is used to set the action condition of the torque limit during vector control.

If inverter output torque is higher than the torque limit, the torque limit function is enabled, so as to control the output torque to be not higher than the upper torque limit for speed control mode. F06.09=0: the torque limit is set by F06.10 and F06.11 F06.09=1: the torque limit is set by AI1* F06.10 and F06.11 F06.09=2: the torque limit is set by AI2* F06.10 and F06.11 F06.09=3: the torque limit is set by AI3* F06.10 and F06.11 F06.09=4: the torque limit is set by AI4* F06.10 and F06.11 219 No. Function Range Unit Default Type F06.09 Speed control torque limit source selection 0: F06.10 and F06.11 1: AI1 2: AI2 3: AI3 4: AI4 (Expansion Card) 5: communication 6: maximum of AI2 and AI3 7:

minimum of AI2 and AI3 0 〇 F06.10 Upper Limit of Electric Torque for Speed Control 0.0 - 250.0 % 165.0 ● F06.11 Upper Limit of Brake Torque for Speed Control 0.0 - 250.0 % 165.0 ●