sinee — 7.7 F06 Group: Vector Control Parameter

EM500 Open-Loop Vector Control Inverter User Manual (F06.05), the movement from switching frequency 1 to switching frequency 2 presents a linear transition procedure. See Figure 7-22 for details. PTD parameter P1,Ti1 P2,Ti2 Switching frequency 1 Switching frequency 2 Feedback frequency Figure 7-22 PI Parameter 1. Generally, user does not need to adjust F06.00 - F06.05 parameters, so please pay enough attention when you decide to adjust these parameters. 2. While setting the switching frequency, please note that the switching frequency 1 (F06.04) must be lower than or equivalent to the switching frequency 2 (F06.05).

When there is overshoot with the speed, properly increase this parameter, if there is no overshoot, try to reduce this parameter and keep the factory setting. The speed loop output filter can reduce the impacts upon current loop, but better not to set a large value for F06.07, which may cause slow response. Generally, user may use the defaults. 218 No. Function Range Unit Default Type F06.06 Speed Loop Anti-Saturation Factor 0.000 - 1.000 0.500 ● No. Function Range Unit Default Type F06.07 Time Constant of Output Filter of Speed Loop 0.000 - 0.100 s 0.001 ● No. Function Range Unit Default Type F06.08 Vector Control Slip Gain 50.00 - 200.00 % 100.00 ●