EM500 Open-Loop Vector Control Inverter User Manual These are optimized parameters for VF control of the synchronous motor. Generally, user adopts the defaults 7.7 F06 Group: Vector Control Parameter Under the vector control mode, inverter adjusts the speed dynamic response of the vector control by adjusting the PI regulator’s speed proportional gain (ASR_P) and speed integral time (ASR_T). Either increasing ASR_P or reducing ASR_T would quicken the speed loop's dynamic response. However, if ASR_P is excessive or ASR_T is insufficient or excessive, this will result in oscillation due to over regulation. User shall adjust the aforesaid PI parameters according to actual load characteristics.
Generally, user shall increase ASR_P as possible and regulate ASR_T, so as to enable the system to response quickly without over control. To enable the system to have a quick dynamic response at both low speed and high speed, it's required to perform PI regulation at both speed modes. In actual running, the speed regulator would automatically calculate present PI parameter according to present frequency. If present PI parameter is below the switching frequency 1, the speed PI parameter is P1, T1; if above the switching frequency 2, the speed parameter PI is P2, T2.
If greater than the switching frequency 1(F06.04), but less than the switching frequency 2 217 Magnetic Flux Compensation of Synchronous Motor No. Function Range Unit Default Type F06.00 Speed Proportional Gain ASR P1 0.00 - 100.00 12.00 ● F06.01 _ Speed Integral Time Constant ASR T1 0.000 - 30.000 0.000: No Integral s 0.200 ● F06.02 _ Speed Proportional Gain ASR P2 0.00 - 100.00 8.00 ● F06.03 _ Speed Integral Time Constant ASR T2 0.000 - 30.000 0.000: No Integral s 0.300 ● F06.04 _ Switching Frequency 1 0.00 - Switching Frequency 2 Hz 5.00 ● F06.05 Switching Frequency 2 Switching Frequency 1 - Maximum Frequency F00.16 Hz 10.00 ●