EM500 Open-Loop Vector Control Inverter User Manual Field weakening control of synchronous motor F06.21=0: Disabled value of motor rotation speed is related to bus voltage of inverter. When the maximum If F06.21=0, the field weakening control will not work. At this time, the maximum speed of motor can not meet the user requirements, user needs to start the field weakening function of synchronous motor for field weakening speed rise. EM500 offers two field weakening modes:
direct calculation mode and automatic adjustment mode F06.21=1 Direct Calculation In the direct calculation method, the required field weakening current is calculated as per the target rotation speed and its size can also be adjusted manually through 06.22. The lower the field weakening current is, the lower the total output current will be, but this may not achieve the required field weakening effect. F06.21=2: Automatic Adjustment In the automatic adjustment method, inverter will select the optimum field weakening current automatically, but this may affect the dynamic performance of the system or cause the system to be unstable.
Setting the proportional gain (F06.24) and the integral time (F06.25) can change the adjustment speed of the field weakening current, but the fast adjustment of the field weakening current may result in instability. Generally, user does not need to make manual modification. initial position autotuning. The value of this parameter is usually got by autotuning and User may adjust the autotuning effect by this parameter when inverter is in the user does not need to set it manually. The higher the injection voltage is, the better the autotuning effect will be. 222 No. Function Range Unit Default Type F06.27 Gain of Autotuning at Initial Position 0 - 600 % 80 ● No.
Function Range Unit Default Type F06.28 Frequency of Injection Current 0.00 - 100.00 (100.00= Motor Rated Frequency) % 10.00 ●