sinee — 7.8 F07 Group: Fault Protection Parameter

EM500 Open-Loop Vector Control Inverter User Manual For example, user only needs to set the first bit of OlP and the third bit of E13 as 1, in order to set OlP and E13 as stop as per the set stop mode (F04.19) in case of a fault. I.e., F07.19=xxx x1x1x. If output current is lower than the offload detection level (F07.22) and this status continues for the offload detection time (F07.23) when the offload detection protection is enabled (F07.21=1) and inverter is in the running mode and not in the DC brake, then inverter gives an offload protection fault (E26) report and stops as the offload protection setting (F07.24). F07.27=0: AVR is disabled. F07.27=1: AVR is enabled.

AVR function has been effective, if the input voltage is lower than the rated input voltage, the voltage and the output frequency is greater than the VF curve corresponding to the frequency, frequency converter will output the maximum voltage in order to make the most of the motor power output; If the input voltage is higher than the rated input voltage, the frequency converter can reduce the output voltage, keep the VF proportion. F07.27=2: AVR is automatic. AVR function automatically effective (decelerating is invalid):

the change of the frequency converter based on the actual power grid voltage, automatically adjust the 231 Correspon 7 6 5 4 3 2 1 0 ding Bit Set Value 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 No. Function Range Unit Default Type F07.21 Offload Protection 0: Disabled 1: Enabled 0 ● F07.22 Offload Detection Level 0.0 - 100.0 % 20.0 ● F07.23 Load Detection Time 0.0 - 60.0 s 1.0 ● F07.24 Offload Protection 0: Coast to Stop 1: Stop as per Set Stop Mode 1 〇 No. Function Range Unit Default Type F07.27 AVR 0: Disable 1: Enable 2: Automatic 1 〇