sinee — 7.8 F07 Group: Fault Protection Parameter

EM500 Open-Loop Vector Control Inverter User Manual The fault retry function can be used to prevent the impact of an accident upon the normal system operation. It is only valid for some faults listed by F07.18. retry, i.e., fault reset. Whether a fault status is outputted by the numeric output terminal When the fault retry function is enabled, a fault will cause inverter to start a fault shall be set through F07.15.

If the fault is still detected subsequent to fault retry, continue with the fault retry until the set fault retry times (F07.14) are reached; if the fault is still detected after the fault retry times, an alarm will be given correspondingly; if the fault does not occur again in several following retries, the fault retry succeeds and inverter continues to work normally.

After the fault retry succeeds, the fault retry times will be cleared if no fault occurs in the recovery time of fault retry times (F07.17), and the fault retry still starts from 0 times when a fault occurs in the future; a fault retry time will be counted based upon the last fault retry count, if the fault still occurs in this retry. These function codes can be used to set inverter action mode when some faults occur. If any of them is set as 0, inverter coasts to stop; if any of them is set as 1, inverter stops as per the set stop mode (F04.19). Such function codes are under the bit operation. Set corresponding position as 0 or 1 Table 7-9 Action Bit at Fault while setting them.

See the table below: 230 F07.17 Recovery Time of Fault Retry Times 0.01 - 30.00 s 10.00 ● F07.18 Fault Retry Ilp HOU HOC SlU SOU SOC **0 00000 〇 0: Permitted 1: Not Permitted No. Function Range Unit Default Type F07.19 Action 1 at Fault E21 E16 E15 E14 E13 E12 Olp Ilp 000 00000 〇 0: Coast to Stop 1: Stop as per Set Stop Mode F07.20 Action 2 at Fault E28 E27 E25 E23 *000 〇 0: Coast to Stop 1: Stop as per Set Stop Mode F07.19 E21 E16 E15 E14 E13 E12 Olp Ilp F07.20 * * * * E28 E27 E25 E23