sinee — 7.8 F07 Group: Fault Protection Parameter

EM500 Open-Loop Vector Control Inverter User Manual Output Frequency (Hz) Time (S) Output Current (%) Time (S) Figure 7-25 Current Limit Action Procedure F07.12 is used to set the action conditions for enabling current limit. If inverter output current exceeds the set value of this function code, current limit function starts to act, so as to control output current at a level not greater than current limit. C urrent limit only works for inverter under the V/F control mode. It's recommended to use this function for occasions of large inertia, fan type load, and the occasion “one inverter shared by multiple motors”. F07.13=0: Disabled The rapid current limit does not work. F07.13=1:

Enabled The rapid current limit can reduce the overcurrent fault. 229 No. Function Range Unit Default Type F07.13 Rapid Current Limit 0: Disabled 1: Enabled 0 〇 No. Function Range Unit Default Type F07.14 Fault Retry Times 0 – 20, 0: Fault Retry Disabled 0 〇 F07.15 Numeric Output Action at Fault Retry 0: Disabled 1: Enabled 0 〇 F07.16 Fault Retry Interval 0.01 - 30.00 s 0.50 ●