EM500 Open-Loop Vector Control Inverter User Manual Inverter is protected for both overvoltage stall and undervoltage stall. If bus voltage is lower than the value set through F07.08 (Undervoltage Stall Control Voltage), inverter will enter the power failure status. If bus voltage is greater than F07.09 (Judgment Voltage at Power Failure Ending), which lasts for the time set by F07.10 (Judgment Delay Time at Power Failure Ending), then inverter returns to the normal status F07.11=0: Disabled Current limit does not work F07.11=1: Limit Mode 1 F07.11=2: Limit Mode 2 limit control is effective (F07.11=1), then the system will automatically start current limit:
During operation, if output current reaches to current limit level F07.12 and current reducing output frequency to restrain the output current from going up, and inverter will quit from over current state. Inverter will return to previous running status, when output current reduces to a value below current limit action level. Current limit action procedure is shown in Figure 7-25. 228 No. Function Range Unit Default Type F07.09 Judgment Voltage at Power Failure Ending Undervoltage Stall Control Voltage - 100.0 % 86.0 ● F07.10 Judgment Delay Time at Power Failure Ending 0.00 - 100.00 s 5.00 ● Defaul No. Function Range Unit Type t F07.11 Current Limit Control 0: Disabled 1: Limit Mode 1 2:
Limit Mode 2 3 〇 F07.12 Current Limit Level 20.0 - 180.0 (100.0= Inverter Rated Current) % 150.0 ●