sinee — 7.8 F07 Group: Fault Protection Parameter

EM500 Open-Loop Vector Control Inverter User Manual F07.06=0: Disabled Overvoltage stall disabled; it’s not recommended to set F07.06 as 0, if there is no external braking unit. Undervoltage stall disabled; F07.06=1: Undervoltage Stall, Enabled When bus voltage is lower than the value set through F07.08, inverter stops after decelerating to zero, and gives an alarm for stable undervoltage fault (SIU). F07.06=2: Overvoltage Stall, Enabled f overvoltage stall is enabled, the stall voltage is set by F07.07. DC bus overvoltage is generally caused by deceleration, because at the time of deceleration, DC bus voltage rises due to energy feedback.

When DC bus voltage is higher than the overvoltage threshold: If the overvoltage stall is enabled (F07.06=2/3) when the DC bus voltage is higher than the overvoltage threshold, inverter stops the deceleration and keeps output frequency unchanged; as a result, the energy feedback stops; until the DC bus voltage backs to normal, inverter starts deceleration again. During the deceleration, the overvoltage stall protection process is shown in Figure 7-24. DC Bus Voltage Overvoltage stall ineffective voltage Overvoltage stall Output frequency Regenerative overvoltage t Figure 7-24 Overvoltage Stall Protection F07.06=3: Overvoltage Stall and Undervoltage Stall, Enabled 227