sinee — 7.8 F07 Group: Fault Protection Parameter

EM500 Open-Loop Vector Control Inverter User Manual To enable this protection, please confirm that present motor has a temperature sensor and transmits the temperature signal to the analog input terminal, and set the temperature sensor type (F07.03) to start motor overheating protection. User may view present motor temperature through the function code F18.38; if motor temperature is greater than motor overheating alarm threshold (F07.05), the numeric output terminal “25:

Motor Overload Pre-alarming” is enabled and this signal is used for instruction; if motor temperature is greater than motor overheating protection threshold (F07.04), inverter will give an alarm about motor overheating fault (E12) and start corresponding protection action. ★ Motor overheating fault (E12) can not be reset immediately until motor temperature drops to a value far below the protection threshold. 226 F07.04 Motor Overheating Protection Threshold 0 - 200 ℃ 110 ● F07.05 Motor Overheating Pre-Alarming Threshold 0 - 200 ℃ 90 ● No. Function Range Unit Default Type F07.06 Bus Voltage Control Options 0: Disabled 1: Undervoltage Stall, Enabled 2: Overvoltage Stall, Enabled 3:

Overvoltage Stall and Undervoltage Stall, Enabled 2 〇 F07.07 Overvoltage Stall Control Voltage 110.0 - 150.0 (380V,100.0=537V) % 131.0 (703V) 〇 F07.08 Undervoltage Stall Control Voltage 60.0 - Judgment Voltage at Power Failure Ending (100.0= Standard Bus Voltage) 76.0 〇