sinee — 7.8 F07 Group: Fault Protection Parameter

EM500 Open-Loop Vector Control Inverter User Manual Figure 7-8 Fault Protection blocking Bit For instance: for shielded IlP protection, only the first bit corresponding to IlP needs to be set as 1, i.e., F07.00=xxxxxx1x For shielded OlP and E13 protection, only the zero bit corresponding to OlP and the fifth bit corresponding to E13 are set to 1, i.e., F07.00=xx1 xxxx1. Please do not shield any protection function unless specially required. Otherwise, inverter may be damaged due to no protection in case of a fault. The inverse-time curve for motor overload protection:

200%Ч(F07.01)ЧMotor Rated Current, for 1 seconds continuously, an alarm is given for motor overload fault (E13); 150%Ч(F07.01)ЧMotor Rated Current, for 15 minutes continuously, an alarm is given for motor overload. User must set F07.01 according to motor’s actual overload capacity. Excessive F07.01 value may easily pose a hazard of motor overheating without an alarm. F07.02 pre-alarm factor is used to determine what degree prior to motor overload protection will trigger an alarm. The higher this factor is, the smaller the advance time of the pre-alarm will be.

If the accumulative output current of inverter is greater than the product of the overload inverse-time curve and F07.02, the multi-function numeric Do of inverter outputs “17: motor overload pre-alarm” ON signal. 225 Protection Code E20 E22 E13 SlU SOU SOC IlP OlP Corresponding Bit 7 6 5 4 3 2 1 0 Set Value 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 No. Function Range Unit Default Type F07.01 Motor Overload Protection Gain 0.20 - 10.00 1.00 ● F07.02 Motor Overload Pre-Alarming Factor 50 - 100 % 80 ● No. Function Range Unit Default Type F07.03 Motor Temperature Sensor Type 0: No Temperature Sensor 1: PT100 2: PT1000 3: KTY84-130/150 4: PTC130/150 0 ●