EM500 Open-Loop Vector Control Inverter User Manual Injection Current F06.29 F06.33 0 Frequency Figure 7-23 High Frequency Injection F06.28 F06.32 At the low frequency range (output frequency determined by F06.29; at the high frequency range (output frequency > F06.32), the injection current is determined through F06.33. User may adjust the gain and the integral time with the regulator to achieve better effects. Generally, user may use the default value. Please do not adjust it if you are not a professional. 7.8 F07 Group: Fault Protection Parameter Bit setting value=0: After detecting the fault corresponding to the bit, inverter will stop output and enter the fault status.
Bit setting value=1: After detecting the fault corresponding to the bit, inverter will not enable the protection and remains the previous status. This code is bit operation. Only corresponding bit has to be set as 0 or 1. See the table below: 224 High F 高req频uen段cy Low 低 Fr频equ段enc y No. Function Range Unit Default Type F07. 00 Protection block E20 E22 E13 SlU SOU SOC IlP OlP 000 00000 0: Valid Protection 1: Protection blocked