sinee — 7.9 F08 Group: Preset Speed and Simple PLC Parameter

EM500 Open-Loop Vector Control Inverter User Manual Attentions: ★ At preset speed running, inverter start/stop is determined by the function code F00.02. ★ At preset speed running mode, inverter acceleration/deceleration time can be Direction at preset speed running is controlled by terminals F/R and RUN. controlled by the external terminal set as the acceleration/deceleration time. In addition to preset speed function, there is simple PLC function, which provides four control modes. See Table 7-11 for details.

233 Setting F00.07 2 Disabled Disabled Disabled Enabled Preset Speed 1 F08.00 3 Disabled Disabled Enabled Disabled Preset Speed 2 F08.01 4 Disabled Disabled Enabled Enabled Preset Speed 3 F08.02 5 Disabled Enabled Disabled Disabled Preset Speed 4 F08.03 6 Disabled Enabled Disabled Enabled Preset Speed 5 F08.04 7 Disabled Enabled Enabled Disabled Preset Speed 6 F08.05 8 Disabled Enabled Enabled Enabled Preset Speed 7 F08.06 9 Enabled Disabled Disabled Disabled Preset Speed 8 F08.07 10 Enabled Disabled Disabled Enabled Preset Speed 9 F08.08 11 Enabled Disabled Enabled Disabled Preset Speed 10 F08.09 12 Enabled Disabled Enabled Enabled Preset Speed 11 F08.10 13 Enabled Enabled Disabled Disabled Preset Speed 12 F08.11 14 Enabled Enabled Disabled Enabled Preset Speed 13 F08.12 15 Enabled Enabled Enabled Disabled Preset Speed 14 F08.13 16 Enabled Enabled Enabled Enabled Preset Speed 15 F08.14 Defau No.

Function Range Unit Type lt F08.15 Simple PLC Running Mode 0: Stop after Single Running 1: Stop after Limited Times of Cycles 2. Run at Last Preset Speed after Limited Times of Cycles 3: Continuous Cycle 0 ● F08.16 Limited Times of Cycles 1 - 10000 1 ●