sinee — 7.9 F08 Group: Preset Speed and Simple PLC Parameter

EM500 Open-Loop Vector Control Inverter User Manual Table 7-11 PLC Running Mode ★ Inverter starts the judgment from the running time of the 15 th preset speed (F08.48) to the first preset speed. A function code not set as 0 is the last preset speed. Output Frequency (Hz) 5 2 1 t (s) 4 12 13 T1 T2 T4 T5 T12 T13 Figure 7-26 Simple PLC Running As illustrated in Figure 7-26, it is the running mode after setting “0: Stop after Single Running”. Since preset speed 3 is set as 0 (F08.24=0.0), inverter will not run at preset speed 3 actually.

Since preset speed 14 and preset speed 15 are set as 0 (F08.46=0.0 and F08.48=0.0), preset speed 13 is the last one and inverter will stop after running at preset speed 13. PLC stop memory function enables inverter to record the running times (F18.10), running stage (F18.11) and present running time (F18.12) of present simple PLC at stop. 234 F08.15 Description 0 Inverter stops after running at the last preset speed. 1 Run circularly; the cycle times is set through F08.16; inverter stops after the cycles are complete.

2 Run circularly; the number of cycle times is set through F08.16; after having completed the running at the last preset speed, inverter keeps running at the last preset speed until a stop command is received. 3 Run continuously and circularly until a stop command is received. No. Function Range Unit Default Type F08.17 Simple PLC Memory Ones Place: Stop Memory 0: Disabled (Start from Preset Speed 1) 1: Enabled (Start at Power Failure) Tens Place: Power Failure Memory 0: Disabled (Start from Preset Speed 1) 1: Enabled (Start at Power Failure) 00 ●