sinee — 7.9 F08 Group: Preset Speed and Simple PLC Parameter

EM500 Open-Loop Vector Control Inverter User Manual Inverter continues with the memorized stage for the running of the next time. If the simple PLC memory function is disabled, the PLC process will be started for every time after inverter restart. PLC power failure memory function enables inverter to record the running times (F18.10), running stage (F18.11) and present running time (F18.12) of present simple PLC before the power failure. Inverter continues with the memorized stage at the next energization. If the PLC power failure memory function is disabled, the PLC process will be started for every time after inverter restart.

To meet different working conditions, the setting for the running time of PLC can be in figures only. Specific meanings shall be set together with the simple PLC time unit (F08.18). There are two time units available. 235 No. Function Range Unit Default Type F08.18 Simple PLC Time Unit 0: s (second) 1: min (minute) 0 ● No. Function Range Unit Default Type F08.19 Setting of Preset Speed 1 Ones Place: Running Direction 0: Forward 1: Reverse Tens Place: Acceleration/Deceleration Time 0: Acceleration/Deceleration Time 1 1: Acceleration/Deceleration Time 2 2: Acceleration/Deceleration Time 3 3:

Acceleration/Deceleration Time 4 0 ● F08.20 Running Time of Preset Speed 1 0.0 - 6000.0 5.0 ● F08.21 Setting of Preset Speed 2 Ones Place: Running Direction 0: Forward 1: Reverse Tens Place: Acceleration/Deceleration Time 0: Acceleration/Deceleration Time 1 1: Acceleration/Deceleration Time 2 2: Acceleration/Deceleration Time 3 0 ●