sinee — 7.10 F09 Group: PID Function Parameter

EM500 Open-Loop Vector Control Inverter User Manual F09.00=0: Numeric PID SettingF09.01 PID setting is done by numeric PID setting, with the specific percentage of F09.01/F09.03 * 100.00%. F09.00=1: AI1 F09.00=2: AI2 F09.00=3: AI3 F09.00=4: AI4 (Expansion Card) The specific percentage of PID setting is directly determined by AI (percentage). F09.00=5: PULSE High-Frequency Pulse (X7) The specific percentage of PID setting is directly determined by HDI (percentage). Please refer to the description of F00.04 for detailed explanations of AI1-AI4 and X7. When they are used for PID setting, their percentages are set values, with the maximum output of 100.00%. F09.00=6:

Communication Percentage Setting The specific percentage of PID setting is directly determined by communication (percentage).  If inverter is under master-slave communication control (F10.05=1) and present inverter is a slave (F10.06=0), the set percentage is “700FH (Master-Slave Communication Setting) * F10.08 (Receiving Proportionality Factor of Slave)”. The range of 700FH is -100.00% to 100.00%. See Table 12-2 for details.  For general communication (F10.05=0), the feedback percentage is “7005 H (Communication Setting of Process PID Feedback)”. The range of 7005 H is -100.00% to 100.00%. See Table 12-2 for details. 241 2: AI2 3: AI3 4: AI4 (Expansion Card) 5:

PULSE High-Frequency Pulse (X7) 6: Communication Percentage Setting F09.01 Numeric PID Setting 0.0 – PID Setting Feedback Range F09.03 0.0 ● F09.03 PID Setting Feedback Range 0.1 - 6000.0 100.0 ●