sinee — 7.10 F09 Group: PID Function Parameter

EM500 Open-Loop Vector Control Inverter User Manual 7.10 F09 Group: PID Function Parameter EM500 inverter has a process PID function, which is to be described in this part. The process PID function is mainly used for pressure control, flow control and temperature control. Kp Ref Ts KpKi  Out + + + + Fdb KpKdTs dt d Figure 7-27 Process PID Block Diagram PID control is a closed loop control mode. The output signal (Out) of the controlled object of the system is fed back to PID controller, which adjusts the output of the controller through PID arithmetic and forms a closed loop or multiple closed loops.

By using PID control, the output value and the set target value of the controlled object are consistent. See Figure 7-27 for the functional block diagram. PID controller implements the control by calculating the three calculation factors, i.e., P (proportional), I (integral) and D (differential) and on the basis of the dispersion between target (Ref) and feedback signal. The features of various calculation factors are as follows: P (proportion) : Proportional control is the easiest control mode. Output error signal and input error signal of its control are proportional. The system outputs the stable error when inverter is in the proportional control only. I (integral):

The integrals of output error signal and input error signal of the controller are directly proportional. This control mode can eliminate the stable error and enable the system to be free from stable error after entering the stable status. However, under this mode, inverter can not track intense changes. D (Differential): The differential values of output error signal and input error signal of the controller are directly proportional. Its controller can predicate the trend of error changes and respond to intense changes to improve the dynamic characteristics of the system in the regulation process. 240 Defau No. Function Range Unit Type lt F09.00 PID Setting Source 0: Numeric PID Setting 1:

AI1 0 〇