sinee — 7.10 F09 Group: PID Function Parameter

EM500 Open-Loop Vector Control Inverter User Manual the status of the input function “PID Positve/Negative Action Switch” together. See Table 7-12 for their relationship details Table 7-12 PID Positive/Negative Action Note: The offset is usually “Setting - Feedback” in PID control.  When feedback signal is greater than PID setting, inverter’s output frequency is required to decrease to make PID reach to a balance. When pressure is higher, the pressure feedback is greater. In this case, inverter’s output frequency falls to reduce  When feedback signal is greater than PID setting, it’s required to increase the pressure and make it constant. PID should be set as positive effect.

inverter output frequency to balance PID. An example is given about supply control: PID regulator shall be in the negative action control 243 F09.04 44: PID Positive/Negative Action mode Description Action Switch 0 0 Positive Action Positive offset and output 0 1 Negative Action Positive offset, but negative output 1 0 Negative Action Positive offset, but negative output 1 1 Positive Action Positive offset and output No. Function Range Unit Default Type F09.05 Proportional Gain 1 0.00 - 100.00 0.40 ● F09.06 Integral Time 1 0.000 - 30.000,0.000:

No Integral s 10.000 ● F09.07 Differential Time 1 0.000 - 30.000 ms 0.000 ● F09.08 Proportional Gain 2 0.00 - 100.00 0.40 ● F09.09 Integral Time 2 0.000 - 30.000,0.000: No Integral s 10.000 ● F09.10 Differential Time 2 0.000 - 30.000 ms 0.000 ● F09.11 PID Parameter Switching 0: Disabled 1: Switching through Numeric Input Terminal 2: Automatic Switching by Offset 0 ● F09.12 PID Parameter Switching Offset 1 0.00 - F09.13 % 20.00 ● F09.13 PID Parameter Switching Offset 2 F09.12 - 100.00 % 80.00 ●