sinee — 7.10 F09 Group: PID Function Parameter

EM500 Open-Loop Vector Control Inverter User Manual To meet different complicated applications, the process PID module has introduced two groups of PID parameters. Parameters can be switched between these two groups through the function setting of F09.11 and the input conditions (input function “43: PID Parameter Switching”, offset e (k), etc.) and performed for linear interpolation.

See Table 7-13 for details Table 7-13 PID Parameter Options As listed in the table above, when the function code F09.11 is set as 0, PID parameters will not be switched and the first group of parameters works; when the function code is set as 1, PID parameters will be switched according to the input function “43: PID Parameter Switching”; when the function code is set as 2, PID parameters will be selected or operated by linear interpolation according to the relationship between the absolute value of present offset e(k) (=|Setting - Feedback|) and the function codes F09.12 and F09.13.

When F09.12≤|e(k)|≤F09.13, present PID parameter is obtained through the linear interpolation of parameters of the first group and the second group. See 7-28 median section for specific principles. 244 Mode Description F09.11 Other Conditions 0 -- Not Switching of PID Parameter, the first group of parameters work 43: PID Parameter PID parameter is switched by the numeric input Switch terminal (43:

PID Parameter Switch) 1 0 Invalid switching, the first group of parameters work 1 Invalid switching, the second group of parameters work |e (k)| - F09.12/13 Automatic Switching by Offset |e (k)| The first group of parameters 2 |e (k)|> F09.13 The first group of parameters Intermediate Value Two groups of parameters are taken as the reference for linear interpolation according to the offset