sinee — 7.10 F09 Group: PID Function Parameter

EM500 Open-Loop Vector Control Inverter User Manual PID Parameter Parameter 1 Parameter 2 100.00% 0 Switching Offset 1 Switching Offset 2 Figure 7-28 PID Automatic Switching of PID Parameters by Offset (F19.11=2) The process PID module outputs PID initial value (F09.14) constantly for PID initial value retention time after inverter starts to run; afterwards, inverter proceeds with PID output regulation. See Figure 7-29 for specific effects. When PID initial value is held for 0.00s, i.e., F09.15=0.00, the output function of PID initial value is disabled.

Output Frequenc y PID Initial Value F09.14 t 0 PID Initial Value Holding Time F09.15 Figure 7-29 PID Initial Value Output 245 ( e ,Y) 1 1 (e ,Y) 2 2 O|f偏fse差t | No. Function Range Unit Default Type F09.14 PID Initial Value 0.00 - 100.00 % 0.00 ● F09.15 PID Initial Value Retention Time 0.00 - 650.00 s 0.00 ● No. Function Range Unit Default Type F09.16 Upper Limit of PID Output F09.17 ~ +100.0 % 100.0 ● F09.17 Lower Limit of PID Output –100.0 – F09.16 % 0.0 ●