sinee — 7.10 F09 Group: PID Function Parameter

EM500 Open-Loop Vector Control Inverter User Manual For PID output limit, the output range of the whole process PID module is F09.17 - F09.16, the actual regulation results are in this scope, with the output at the boundary. When the offset between PID setting and feedback is less than and equal to the offset limit (F09.18), PID stops the regulation. In this way, when the offset between the setting and the feedback is low, output frequency stabilizes, which works for some closed loop control occasions. When the input terminal function “41: Process PIC Pause” is enabled, PID can also stop the regulation. User may use these two methods together.

The differential (D) component of PID regulator can not be greater than PID differential limit value (F09.19) to avoid excessively high offset, otherwise the output is also greater and causes the system oscillation. Properly setting this value can affect the impact of the occasional interference upon the system. To perform PID regulation in a faster and better way, it's not required to conduct the integral regulation temporarily sometimes, but only PD or P regulation. EM500 inverter has a particular integral separation function:

When the offset between PID setting and feedback is greater than PID integral separation threshold (F09.20), the integral separation is enabled, i.e., the integral (I) regulation function of PID regulator pauses. The input terminal function “42: Process PID Integral Pause” can be used together for 246 No. Function Range Unit Default Type F09.18 PID Offset Limit 0.00 - 100.00, (disabled at 0.00) % 0.00 ● No. Function Range Unit Default Type F09.19 PID Differential Limit 0.00 - 100.00 % 5.00 ● Function Name of Prop Parameter Description Unit Default Code Function Code erty F09.20 PID Integral Separation Threshold 0.00 - 100.00, (100.00%=Integral Separation Disabled) % 100.00 ●