sinee — 7.10 F09 Group: PID Function Parameter

EM500 Open-Loop Vector Control Inverter User Manual remote control. If the function code setting is disabled (F09.20=100.00), the input terminal function does not work. See Table 7-14 for details Table 7-14 Integral Separation Function Description 100.0%. It is similar to an acceleration/deceleration function.If PID setting changes, the PID setting variation time refers to the time required for the change from 0.0% to actual setting value of PID will have a linear change to reduce the impact incurred upon the system. After the initial value is set, the smooth setting will be invalid.

reducing the interference impact upon the feedback, but causes the response performance F09.22 is used for filtering of PID feedback. The filtering action is in favour of of the closed loop system of the process to go down. F09.23 is used to filter PID output. The filter can reduce the possibility of sudden change of inverter output frequency, but this can also reduce the response performance of process closed loop system. 247 Mode Description F09.20 DI (42) F09.20: PID Integral Separation Threshold;DI (42):

Process PID Integral Pause 100.00% -- The integral (I) is always enabled 0.00% - 99.99% Up to the relationship between |e (k)| and F09.20, and the status of DI Disabled If |e (k)| >F09.20, the integral separation will be enabled Enabled Integral Separation Enabled No. Function Range Unit Default Type F09.21 PID Setting Variation Time 0.000 - 30.000 s 0.000 ● Function Name of Function Parameter Description Unit Default Property Code Code F09.22 PID Feedback Filter Time 0.000 - 30.000 s 0.000 ● F09.23 PID Output Filter Time 0.000 - 30.000 s 0.000 ● No. Function Range Unit Default Type F09.24 Upper Limit Detection 0.00 - 100.00 % 100.00 ●