sinee — 7.10 F09 Group: PID Function Parameter

EM500 Open-Loop Vector Control Inverter User Manual Recommendation: During the positive action, F09.28 (awakening action point) ≥ F09.30 (awakening action point); during negative action, F09.28 (awakening action point) ≤ F09.30 (awakening action point). These function codes are used for PID setting together with the function code. EM500 inverter has the preset PID setting function, for which the switching condition is mainly determined by the input function “15: Preset PID Terminal 1” and “16: Preset PID Terminal 2”. See Table 7-16 for details.

Table 7-16 Preset PID Setting Function 250 point (F09.28) and this status is maintained for the awakening delay time (F09.31), inverter exits the sleep mode ★During the delay, function code sets output; after the delay, PID continues with the normal output No.

Function Range Unit Default Type F09.32 Preset PID Setting 1 0.0 – PID Setting Feedback Range F09.03 0.0 ● F09.33 Preset PID Setting 2 0.0 – PID Setting Feedback Range F09.03 0.0 ● F09.34 Preset PID Setting 3 0.0 – PID Setting Feedback Range F09.03 0.0 ● Mode Setting Range Setting 16 15 F09.00 Disabled Disabled 0 F09.01 0.0 - F09.03 0.00% - 100.00% 1 AI1 -100.00% - 100.00% -100.00% - 100.00% 2 AI2 -100.00% - 100.00% -100.00% - 100.00% 3 AI3 -100.00% - 100.00% -100.00% - 100.00% 4 AI4 -100.00% - 100.00% -100.00% - 100.00% 5 HDI -100.00% - 100.00% -100.00% - 100.00% 6 485 -100.00% - 100.00% -100.00% - 100.00% Disabled Enabled -- F09.32 0.0 - F09.03 0.00% - 100.00% Enabled Disabled -- F09.33 0.0 - F09.03 0.00% - 100.00% Enabled Enabled -- F09.34 0.0 - F09.03 0.00% - 100.00%