sinee — 7.11 F10 Group: Communication Function Parameter

EM500 Open-Loop Vector Control Inverter User Manual A read only parameter of communication card. Communication card function, as shown in the communication card manual. EM500 inverter support CANSinee communication protocol based on CAN, which realize the communication between PC or PLC with inverter or more communication between the inverters. When the Inverter as a slave into the bus, must have its own unique address. The setting range is 1 ~ 31, that is, the whole network supports up to 31 slaves. ★ 0 is the broadcast address, all the inverters can be identified from the machine, this address does not need to set.

EM500 series inverter supports 4 different baud rates.With the upper computer or multi-machine communication, the inverter / host computer needs to be set to the same baud rate. The baud rate will affect the communication distance See Chapter 13 for more information. 260 No. Function Range Unit Default Type F10.48 Communication Card Software Version × No. Function Range Unit Default Type F10.49 number of process data received 1~16 2 ● F10.50 number of process data transmission 1~16 2 ● F10.51 Process data address setting mode selection 0:keypad 1:Master 0 ● F10.52 Communication card manual reset selection 0:disable 1:enable 0 ● No.

Function Range Unit Default Type CANSinee F10.53 Communication 1~31 1 〇 address No. Function Range Unit Default Type 0:125K CANSinee 1:250K F10.54 Communication 0 〇 2:500K baud rate 3:1M