sinee — 7.13 F12 Group: Keypad and Display Parameter

EM500 Open-Loop Vector Control Inverter User Manual  2: All Locked Except this Function Code Under the parameter locking mode, no function code can be set except this function code. This mode is mostly applied to the working conditions that the parameters have been set and debugged and no parameter setting is required. Under this mode, user only run, stop and monitor inverter. As for a working condition that multiple inverters shall run under the same parameter settings, user may debug one inverter; set F12.03=1 for it, and upload the set parameters to the keypad for temporary saving; then set F12.03=2 for the rest inverters, and now download the parameter settings to them.

By using this function, user may set parameters of multiple inverters quickly. User may set most function codes at first even if there are still individual parameters with different settings, and user may complete the setting of such individual parameter settings by other methods. (See 4.5 Parameter Copy) 265 F08.07 Preset Speed 8 F09.34 Preset PID Setting 3 F08.08 Preset Speed 9 F13.03 Preset Torque 1 F08.09 Preset Speed 10 F13.04 Preset Torque 2 F08.10 Preset Speed 11 F13.05 Preset Torque 3 No. Function Range Unit Default Type F12.03 Parameter Copy 0: No Autotuning 1: Upload Parameter to Keypad 2: Download Parameter to Inverter 0 〇 No.

Function Range Unit Default Type F12.04 LED Display Parameter 1 00000000 - 11111111 (o for non-displaying, 1 for displaying) bit0: Output Frequency bit1: Set Frequency bit2: Output Current bit3: Output Voltage bit4: DC Bus Voltage bit5: Output Power bit6: Output Torque bit7: Torque Setting 000 11111 ● F12.05 LED Display 00000000 - 11111111 (o for 000 ●