sinee — 7.13 F12 Group: Keypad and Display Parameter

EM500 Open-Loop Vector Control Inverter User Manual often uses STOP RESET of keypad to stop inverter for purpose of eliminating risks, which is the fastest way. However, during the normal running of inverter, it is the most convenient way to stop inverter through the keypad. Therefore, the function code F12.01 is added and the default setting is that the STOP button is always enabled. ★ It’s not recommended to modify this function code. If necessary, please pay enough attention. In order to avoid unnecessary risks caused by misoperation or non-personnel operation of keypad, the keypad has the parameter locking function.

If the default setting of this function code is “unlocked”, you can set all function codes; after all the function codes are debugged according to the working conditions, user may lock parameters.  1: Reference Input, Unlocked Under the parameter locking mode, no function code can be modified except the function codes with the reference input and this function code. Specific function codes with the inference input are indicated in Table 7-17: Table 7-17 Function Codes with Reference Input 264 No. Function Range Unit Default Type F12.02 Parameter Locking 0: Unlocked 1: Reference Input, Unlocked 2: All Locked Except this Function Code 0 ● No. Function No.

Function F00.07 Numeric Frequency Setting F08.11 Preset Speed 12 F08.00 Preset Speed 1 F08.12 Preset Speed 13 F08.01 Preset Speed 2 F08.13 Preset Speed 14 F08.02 Preset Speed 3 F08.14 Preset Speed 15 F08.03 Preset Speed 4 F13.02 Numeric Torque Setting F08.04 Preset Speed 5 F09.01 Numeric PID Setting F08.05 Preset Speed 6 F09.32 Preset PID Setting 1 F08.06 Preset Speed 7 F09.33 Preset PID Setting 2