sinee — 7.13 F12 Group: Keypad and Display Parameter

EM500 Open-Loop Vector Control Inverter User Manual Operation Monitoring); now, press >> to switch among parameters circularly. Function User may press ESC to enable inverter to enter the monitoring mode (see 4.4 codes F12.04 - F12.05 are used to select which parameters are to be displayed, i.e., the parameters are in a circular display queue. The selected options correspond to the F18 Group: Monitoring Parameter, so user may enter F18 to view present values of all parameters. This function is mainly for fast display, especially during the running period.

Under default conditions, the circular display queue only displays some commonly used options, respectively output frequency (F18.00), set frequency (F18.01), output current (F18.06), output voltage (F18.08) and DC bus voltage (F18.09). If other parameters are required for display, please set these parameters as 1; if not, set them as 0. ★ Please pay enough attention when retaining some function codes Inverter output is mostly displayed in frequency. To get to know present load speed (F18.13), user may set present parameter according to actual working conditions, so as to convert the frequency output into the speed output; as a result, F18.13 would be used to display present load speed.

If F12.09=30.00 (this value is relative to pole-pairs, device transmission ratio, etc.), then output frequency 0.00 - 50.00 Hz corresponds to the load speed 0 - 1500 rpm. 267 bit1: VF Separation Output Voltage bit2: VF Separation Target Voltage bit3: Motor Temperature bit4 - bit7: Not Used No. Function Range Unit Default Type F12.09 Load Speed Display Factor 0.01 - 600.00 30.00 ● No. Function Range Unit Default Type F12.10 UP/DOWN Acceleration/Decele ration Rate 0.00: Automatic Rate 0.01 - 500.00 Hz/s 5.00 〇 F12.11 UP/DOWN Offset Clear 0: Not to Clear 1: Clear at Non-Running Status 2: Clear at Disabled UP/DOWN 1 〇