EM500 Open-Loop Vector Control Inverter User Manual By setting this parameter as 1, user may reset all parameters except motor parameter (F01 group), inverter parameter, manufacturer parameter, power-on time (F12.15/16) and running time (F12.17 and F12.18) ★ This operation is irreversible. Please pay enough attention while operating. F12.15 and F12.16 are used together to view the accumulated power-on time from the production of inverter until now (as per the time that inverter is powered on). This value will be accurate to 1 minute, and up to about 65,536 hours (about 7.5 years). inverter is 2 days 2 hours and 33 minutes.
If F12.15=50 and F12.16=33, it means that the accumulated power-on time of ★ These parameters are used for viewing only and can not be operated or cleared F12.17 and F12.18 are used together to view the accumulated power-on time from the production of inverter until now (as per the time that inverter runs). This value will be accurate to 1 minute, and up to about 65,536 hours (about 7.5 years). If F12.17=47 and F12.18=39, it means that inverter has run for 1 day and 23 hours and 39 minutes. ★ These parameters are used for viewing only and can not be operated or cleared 269 manufacturer parameter, running and power-on time record) No.
Function Range Unit Default Type F12.15 Accumulated Power-On Time h 0 - 65535 h 0 × F12.16 Accumulated Power-On Time mi 0 - 59 min 0 × No. Function Range Unit Default Type F12.17 Accumulated Running Time h 0 - 65535 h 0 × F12.18 Accumulated Running Time (min) 0 - 59 min 0 ×