sinee — 7.19 F18 Group: Monitoring Parameter

EM500 Open-Loop Vector Control Inverter User Manual 305 F18.14 Load Speed Display present load peed. For normal display, please set the load speed display factor (F12.09). Range: 0 - 65535. rpm F18.15 UP/DOWN Offset Frequency Used to display UP/DOWN offset frequency. For details, please refer to the descriptions of UP/DOWN Function of F12.10 - F12.12. HHz F18.16 PID Setting Used to display present PID setting; divide it by F09.03 to get present percentage setting. F18.17 PID Feedback Used to display present PID feedback; divide it by F09.03 to get present percentage setting. F18.18 Kilowatt-Hour Meter, MWh Used to display the accumulated input (output + fan) energy consumption (MWh).

Used together with F18.19 to confirm present energy consumption. MWh F18.19 Kilowatt-Hour Meter, kWh Used to display the accumulated input (output + fan) energy consumption (kWh). Used together with F18.18 to confirm present energy consumption. kWh F18.20 Output Power Display present output power. Range: 0.00 - 650.00. kW F18.21 Output Power Factor Display present output power factor. Range: -1.00 - 1.00. F18.22 Numeric Input Terminal Status 1 Display present active status of input terminals X1 - X5. The five-digit nixie tube will display the following information from left to right: X5 X4 X3 X2 X1 0/1 0/1 0/1 0/1 0/1 Actual display: 00001 ★ 0: disabled; 1: enabled.

F18.23 Numeric Input Terminal Status 2 Display present active status of input terminals X6/X7/AI1 - AI3. The five-digit nixie tube will display the following information from left to right: AI3 AI2 AI1 X7 X6 0/1 0/1 0/1 0/1 0/1 Actual display: 00000 ★ For EM500 inverter, analog input terminals AI1 - AI3 can be used for numeric input only. ★ 0: disabled; 1: enabled. F18.24 Numeric Input Terminal Status 3 Display present active status of input terminals X8 - X11/ AI4. The five-digit nixie tube will display the following information from left to right: AI4 X11 X10 X9 X8 0/1 0/1 0/1 0/1 0/1