sinee — 7.21 F25 Application of water supply basic groups

EM500 Open-Loop Vector Control Inverter User Manual F25.45=1: Maintain the status quo. This function is available only in master-backup mode. When the motor overload occurs and the output phase loss fault occurs, the inverter will automatically switch to the currently unused pump. At this time, the inverter will continue to run, and the keypad will display C005 (motor overload in rotation) / C006 (phase loss during rotation) warning. If another fault occurs, it will stop. If a fault occurs when switching to an unused pump, the machine stops as a normal fault. F25.46=0: All Stop The system will stop according to the set stop mode, enter the fault state. F25.46=1: Maintain the status quo.

The system will continue to run at the current output frequency, and the inverter will display C002 warning until it receives the stop command, emergency stop command, external overpressure signal and water shortage signal. F25.47 Ones Place=0: Fault: The inverter enters the overpressure fault condition. F25.47 One Place=1: Alarm: Overpressure pipe network is shielded, the system continues to run, the corresponding warning display on the keyboard, while the overpressure alarm output terminal is valid, but does not affect the system to continue running. When the overpressure disappears, the alarm is automatically canceled. 319 No.

Function Range Unit Default Type F25.46 Feedback disconnection handling 0:All Stop 1: Maintain the status quo. 0 〇 No. Function Range Unit Default Type F25.47 Pipe network overpressure alarm handling Ones Place: Overpressure alarm selection 0: Error 1: Alarm Tens Place:Switching mode under overpressure 0: Not Used 1:Scram standby 10 〇