sinee — 7.21 F25 Application of water supply basic groups

EM500 Open-Loop Vector Control Inverter User Manual When the water supply pool function is in effect, the water level given value is adjusted according to the water level. The pressure given value for the water level control of the Inlet pool is normally set to a value less than the normal set pressure. F25.44=0: Disabled Sewage water level detection function is invalid, sewage pump terminal function output is invalid. F25.44=1: Enabled After setting the sewage water terminal secondary function, sewage pool water level detection function effectively, sewage pump terminal function is controlled according to the sewage pool water level. Sewage pump control logic:

When the sewage pool water level limit signal is valid and the lower limit water level signal is valid, start the sewage pump, when the sewage pool water level lower limit signal is valid, stop the sewage pump. F25.45=0: All Stop A failure occurs, the normal failure stop 318 Analog input value upper limit water level switch lower limit water level switch shortage water level switch >F25.40 closed closed closed >F25.41 Open closed closed >F25.42 Open Open closed Open Open Open No. Function Range Unit Default Type F25.43 Non-normal standby pressure F25.03~F09.01 %/ MPa 0.1 〇 No. Function Range Unit Default Type F25.44 Sewage pool water level detection function 0: Disabled 1: Enabled 0 〇 No.

Function Range Unit Default Type F25.45 Inverter fault handling 0:All Stop 1: Maintain the status quo. 0 〇